| System
Specifications |
| |
Capable of monitoring 1,390 addressable points
(sum of detectors and modules) |
| |
Addressable
Control Module(M500CH) for output point control
incorporating external power for circuit tripping
|
| |
Each
loop able to accommodate up to 99 addressable
detectors and 99 input/output modules. |
| |
Addressable
Isolator Module(M500X) to isolate section with
a short-circuit |
| |
System
password to prevent unauthorised access |
| |
Addressable
Monitor Module(M500MB) for voltage-free contact
inputs |
| |
Provision
of 145 field programmable output control sequence
during system alarm |
| |
Interface
with 20 x 2 character LCD display with integral
keypad |
| |
Latched
alarm detection |
| |
Printer
interface for system report |
| |
Loop
line open/short circuit protection |
| |
Optimal
mimic diagram interface complete with LED indication
panel |
| |
Fully
field programmable |
| |
Optional
14" monochrome monitor and keyboard |
| |
2
stage alarm bell program & 3 level alarm sensitivity
selection |
| |
Optional
Colour Graphic complete with system software |
| |
Pre-alarm
warning status |
| |
Optional
LED annunciator for alarm, fault isolate and other
status information |
| |
Emergency
evacuation annunciation |
| |
Optional
repeater panel for status annunciation at remote
locality. |